Multi-setting, according to input power condition user can be set as 1/1, 1/3, 3/1 or 3/3 system.
It's designed with modular structure and is made up of 1-10 modules
It's fitted with redundancy and can be upgraded according to your specific requirements
N+X redundant technique, thus ensuring the reliable performance of the system
The batteries can be shared
The input THDI is not more than 5%
Out modular UPS is environmentally friendly, small in size and light in weight.
It's easy to maintain. The module can be replaced optionally.
System controller is used to carry out communications and diagnosis.
Uses centralized static switch module
(2) UPS Modules
Expansion easily according to demand to choose capacity collocate
Online double conversion design, assure the output quality.
Every module has digital and intelligent control separately.
Every module just and independent UPS, can work independently.
Every module has independent charging system.
Hot swappable, it ensure online maintenance.
Standard dimension: 2U × 19 × 520mm
Technical Specifications of Module UPS, MPS9330 5KVA-210KVA
When the frequency of utility power is 50HZ± 2%, the output frequency of UPS follows the utility power frequency, and the phase difference is < 3° ; when the frequency of utility power is beyond the 50Hz± 0.2% or when the battery offers power, the output frequency is 50Hz± 0.2%.
Power factor
0.8
Harmonic Distortion
Linear load ≤ 3%, non-linear load ≤ 5%
Current Crest Ratio
3: 1
Whole unit efficiency
≥ 95% (AC power) ≥ 98%(Battery Powered)
Current sharing accuracy
≤ 5%
Transfer time
0ms
Dynamic response transient range
Overload 10%~100%or 100%~10%, the output voltage is ≤ 2%
Load unbalance capability
Can endure 100%unbalanced load
DC
Input rated voltage
± 384V
Input voltage range
345V~440V
Panel display
LCD
Chinese/English display UPS status, input voltage, output voltage, current, frequency, battery voltage, charge-discharge current value, fault and warning.