Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | GP9335C 120-800KVA | ||||||||||||
6P | 6P | 12P | 6P | 12P | 6P | 12P | 6P | 12P | 12P | 12P | 12P | ||
Rated Nominal | 120KVA/108KW | 160KVA/144KVA | 200KVA/180KW | 300KVA/270KW | 400KVA/360KW | 500KVA/450KW | 600KVA/540KW | 800KVA/720KW | |||||
Rated input voltage | 380/400/415VAC 3-phase 4-wire | ||||||||||||
Rated frequency | 50/60HZ | ||||||||||||
Input parameters | |||||||||||||
Input voltage range | ±25% | ||||||||||||
Input frequency range | 45Hz~65Hz | ||||||||||||
Input soft start function | 0-100% 5-300settable | ||||||||||||
Input power factor | >0.98(If harmonic filter is added) | ||||||||||||
Input harmonic current (THDi) | <4.5%(If harmonic filter is added) | ||||||||||||
Bypass | |||||||||||||
Bypass voltage range | -20%~+15% | ||||||||||||
Bypass frequency range | 50/60HZ±10% | ||||||||||||
Output parameters | |||||||||||||
Inverter output voltage | 380/400/415VAC 3-phase 4-wire | ||||||||||||
Voltage stability | ±1%(Steady status),±3%(Transient status) | ||||||||||||
Frequency | 50/60Hz | ||||||||||||
Mains power synchronization window | ±5% | ||||||||||||
Actually measured frequency accuracy (internal clock) | 50/60Hz±0.05Hz | ||||||||||||
Output power factor | 0.9(Output 90kW per 100kVA) | ||||||||||||
Transient response time | <5ms | ||||||||||||
Inverter overload capability | At 0.9 power factor, 110% for 1 hour, 125% for 10 minutes and 150% for 60s | ||||||||||||
Short circuit current from inverter | 3ph 1.5ln for 5seconds,1ph 2.9ln for 5seconds | ||||||||||||
DC Voltage | 360/384/432/480VDC | ||||||||||||
Maximum Bypass Capability | 100% for 100ms | ||||||||||||
Phase Shift Characteristic | with 100% balanced load | <1° | |||||||||||
with 100% balanced load | <1° | ||||||||||||
Total Harmonic Distortion(THDv) | 100% linear load | <1% | |||||||||||
100% non-linear load | <3% | ||||||||||||
System efficiency (full load) | Up to 94% (inverter efficiency is up to 98%) | ||||||||||||
Rectifier output parameters | |||||||||||||
Charger output voltage stability | 1% | ||||||||||||
DC ripple voltage | ≤1% | ||||||||||||
Operating environment | |||||||||||||
Operating temperature range | 0~40°C | ||||||||||||
Storage temperature | -25~70°C(Without battery) | ||||||||||||
Relative humidity | 0~95% No condensation | ||||||||||||
Maximum Operating Height | ≤Elevation 1000m, for elevation above 1000m, derate by 1% for every increase of 100m | ||||||||||||
Noise (1m) | 58-68dB | ||||||||||||
Protection level | IP20 | ||||||||||||
Standard | Safety: IEC60950-1 IEC62040-1-1 UL1778 EMC IEC62040-2 CLASS C2 EN50091-2 CLASS A Design and Test IEC62040-3 | ||||||||||||
Physical Parameters | |||||||||||||
Weight(kg) | 980 | 1420 | 11200 | 1750 | 1350 | 2000 | 1600 | 2200 | 2100 | 2750 | 3690 | 6390 | 7390 |
Dimension(WxDxh)mm | 900X855X1900 | 1250X855X1900 | 1640X855X1900 | 1250X855X1900 | 1640X855X1900 | 2280X855X1900 | 2385X1000X1950 | 3955X1090X1950 |